Item 14
To permit existing signs and directional signs to remain
wherein they may not comply or be in complete compliance
with AS 2293.1.
Exemptions from the requirements of the following clauses
are necessary:
E4.8, E4.8(a), E4.8(b).
Item 15
To permit each principal fire compartment in the patient care areas, to be provided with at least one exit in lieu of an exit being provided from each required smoke compartment.
Exemption from the requirements of the following clauses are necessary: D1.2(e)
Item 16
To permit the maximum distances of travel from small areas on most floors to exceed those prescribed.
Exemption from the requirements of the following clauses are necessary: D1.4, D1.4(c), D1.4(d)
Item 17
To permit the existing exits to remain in their present location on Level 2 to 10 where the maximum distance between them, of 45m, as prescribed for patient care areas, is exceeded.
Exemptions from the requirements of the following clauses are necessary: D1.5, D1.5(a), D1.5(b)
Item 18
To permit existing corridors and passageways to remain wherein they are paths of travel to exits and have widths of less than 2m.
Exemptions from the requirements of the following clauses are necessary: D1.6(b)