To permit existing materials to remain where they may not comply with the indices limitations prescribed in Specification C1.10.

Exemptions from the requirements of the following clauses are necessary: 01.10, specification 01.10

Item 11

To permit the firemains and water supply services to be upgraded wherein water storage tanks, with sufficient capacity will not be provided.

Exemption from the requirements of the following clauses are necessary: E1.2, Specification E1.2, E1.2(a), E1.2(b), E1.2(c), E1.2(d), E1.2(e), E1.2(f)

Item 12

To permit the hose reels to remain wherein they may not be located as required and may not comply in all respects with AS 1221 and AS 2441.

Exemptions from the requirements of the following clauses are necessary: E1.4, E1.4(a), E1.4(b), E1.4(c), E1.4(e)

Item 13

To permit the existing hydrants to remain as located and the installation of an additional hydrant, adjacent to Stair 3, on all levels, to the satisfaction of the Fire Brigade, wherein all hydrants will not be located not more than 4m from a required exit and all areas will not be within a 6m spray of water, from the nozzle end, of a fully extended 30m length of hose.

Exemptions from the requirements of the following clauses are necessary: E1.3 (c)